+7 (777) 777-88-87
Время работы ПН-ПТ с 09.00 до 18.00

SiFire-EN-100/315-296-160EJ

Производитель
Wilo
Артикул
4241524
43071955

Pressure boosting system as a fully automatic compact unit for fire fighting purposes in accordance with EN 12845.

Consisting of a main pump with horizontal base frame — EN 733 — with spacer coupling, electric motor and multistage vertical electric jockey pump, diaphragm pressure vessel (capacity: 20 l) and one switch cabinet per pump, fixed to a robust support structure.

Model SC-Fire E for the electric motor, equipped with Smart Controller, plus model SC-Fire J for the jockey pump, solid construction made of special profiled parts with cut-outs for forklift trucks and hooks to ensure trouble-free, safe transportation. Height-adjustable bracket for the outlet manifold and special base plate which reduces the transfer of vibrations considerably and increases the reliability and service life.

A circuit with dual pressure switch, pressure gauge, non-return valve, valve (secured from use by unauthorised personnel) for the main pump for automatic start. The cables are concealed in the construction and protected against bumps and cuts. Equipped with a diaphragm installed directly on the main pump housing as standard, to prevent overheating in the event of zero flow.

Switchgears SC-Fire E and SC-Fire J for fire extinguishing systems in accordance with EN 12845.

Switchgears integrated in a sheet metal enclosure in accordance with protection class IP54.

Very high quality control system and particularly easy operation thanks to SC Fire control, with symbol-based LC display, simple user interface with clear menu layout, pressure and rotary switches for quick adjustment of parameters. Communicative controller for monitoring system operation.

The system has been mounted on the base frame with wires and pipes are ready for connection.

Inlet pressure:

The maximum inlet pressure must be taken into account when designing the system configuration (see Technical data). The maximum permissible inlet pressure is calculated from the maximum operating pressure of the system minus the maximum pumping head of the pump at Q = 0. For sprinkler systems in accordance with EN 12845, the water pressure should not exceed 12 bar. In sprinkler systems with a pronounced slope, in which the difference in height between the highest and lowest sprinkler is more than 45 m, the water pressure can be higher than 12 bar at the pump outlet or in the piping, provided that all of the system components are designed for this pressure level.

Installation of the pressure boosting pump under suction conditions.

For the main pump, it is necessary to install a supply tank with connection to the discharge pipe above the pump.

Volume flow

Up to 750 m³/h (208 l/s) system configuration for the main pump.

Switchgears/control devices for fire water supply systems

Wilo-Control SC-Fire E (main pump with electric motor)

Hardware:

Fully electronic central control unit, installed in a painted steel enclosure, protection class IP54, control and display devices on the front door

Features and functions:

The design of the control device depends on the power of the connected pump (start via DOL or star-delta connection). The device comprises the following components:

  • Main switch: For switching the switchgear on and off. (For unauthorised use in the event of a fire)
  • Display: Display built into the door of the switch cabinet for operation and display purposes. Shows the operating data and the operating status of the pump and controller through a combination of symbols and numerical codes. Menu selection and parameter input is effected via the red button
  • Microprocessor with Soft PLC: Microprocessor PLC (Soft PLC), realised through programming, the power supply unit and the I/O wiring. The programming configuration depends on the system and the sprinkler system
  • Indicators: Longlife signal lamps indicate the operational readiness and operation of the pump, the activation of the pressure switch and the float switch, a false start, a collective error, manual start and manual stop
  • Buttons: Push buttons for manual start and manual stop, the lamp test and acknowledgement of alarms and warning messages
  • Fuse protection: Fuses which tolerate the starting current for at least 20 s
  • Motor startup: Contactor for direct-on-line starting, up to 22 kW, for higher power levels start via star-delta connection
  • Motor protection: Only for signalling
  • Monitoring of the water supply: By means of a float switch to ensure a minimum water level of 2/3 of the supply tank is always maintained
  • Performance monitoring: Power supply and performance of the pump
  • Combined signal report: All types of error are displayed via a common error indicator
  • Individual signal report: The important false start error message is displayed via an individual error indicator
  • Error message and acknowledgement: All error messages are displayed via LEDs, shown in the display as an error code and must be acknowledged

Software:

  • Factory-programmed for fully automatic operation
  • Information regarding voltage, electric current and power of the pump
  • Menu navigation with symbol representation

Conforms to the following standards:

  • Fixed Firefighting Systems — Automatic Sprinkler Systems — (EN 12845), part for pumps with electric motor
  • Electrical Equipment of Machines (EN 60204-1)
  • Low-voltage Switchgear and Controlgear Assemblies (EN 61439-1 and EN 61439-2)
  • EMC — Electromagnetic Compatibility for Industrial Environments (EN 61000-6-2)
  • EMC — Emission Standard for Residential, Commercial and Light-Industrial Environments (EN 61000-6-3)

Function description:

Wilo SC-Fire E control devices can be used to control pumps with an electric motor, sensors for pump management and the level of information. The SC-unit is controlled via a microprocessor with Soft PLC. It is used to control and regulate the necessary functions of pressure boosting systems for fire fighting in accordance with EN 12845 for test purposes and operation of the sprinkler system.

The operating logic for the fire extinguishing unit is based on the cascade calibration of the pressure switches for starting the pump.

If a large amount of water is requested due to the opening of one or more circuits or due to a defective sprinkler, the pressure in the system decreases. The SC-Fire controller then initiates a startup of the main pump. As soon as the sprinkler circuit or gate valve via which the sprinkler heads are supplied is closed, holding pressure (resting pressure) is built up in the system. The stop buttons on the SC-Fire must then be actuated to stop the main pump.

Additional information:

A significant advantage offered by the Smart Controller SC-Fire is the user friendliness of the tried and tested Wilo red-button technology. At the heart of the SC is the Soft PLC programmable logic controller, which is based exclusively on Wilo's wealth of experience. All programming is implemented internally. These next generation control devices can therefore be used flexibly and fulfil customer-specific requirements in all markets.

Wilo-Control SC-Fire J (jockey pump with electric motor)

Hardware:

Fully electromechanical control unit, installed in a painted steel enclosure, protection class IP54, control devices and buttons on the front door

Features and functions:

The design of the control device depends on the power of the connected pump. The device comprises the following components:

  • Main switch: For switching the switchgear on and off
  • Indicators: Longlife signal lamps, which indicate the operational readiness of the pump, operation of the pump and collective errors
  • Switches: Rotary switch for setting the manual mode or automatic mode
  • Motor startup: Direct contactor
  • Motor protection: Switch for protection against short-circuits and overloads
  • Individual signal report: Motor error message (short-circuit, overload)
  • Error message and acknowledgement: The motor error message is indicated via corresponding LEDs. The error is acknowledged when the motor protection switch is restarted

Conforms to the following standards:

  • Fixed Firefighting Systems — Automatic Sprinkler Systems — (EN 12845), part for jockey pumps
  • Electrical Equipment of Machines (EN 60204-1)
  • Low-voltage Switchgear and Controlgear Assemblies (EN 61439-1 and EN 61439-2)
  • EMC — Electromagnetic Compatibility for Industrial Environments (EN 61000-6-2)
  • EMC — Emission Standard for Residential, Commercial and Light-Industrial Environments (EN 61000-6-3)

Function description:

Wilo-Control SC-Fire J units can be used to control jockey pumps with an electric motor and sensors according to EN 12845, as well as for test purposes and operation of the sprinkler system.

The operating logic for the fire extinguishing unit is based on the cascade calibration of the pressure switches for starting the pump.

The jockey pump, which is used for pressure boosting, is started first and ensures that the system is filled with water and that it remains pressurised. It is activated in the event of a pressure drop in the system. A properly calibrated pressure switch is used for controlled starting and stopping procedures.

Motor data
Protection class switchgear
IP54 
Rated speed
2980 1/min
Rated power
160 kW 
Power factor
0.89 
Rated current
269.45 A
Mains connection
3~400 V, 50 Hz 
Product data
Product description
SiFire-EN-100/315-296-160EJ 
Colour
Red/black/silver 
Date of sales availability
2020-09-20 
Article number
4241524 
Minimum order quantity
EAN number
4062679082707 
Brand
Wilo 
Hydraulic data
Max. fluid temperature
50 °C
Max. ambient temperature
40 °C
Maximum operating pressure
16 bar
Min. ambient temperature
4 °C
Maximum inlet pressure
6 bar
Min. fluid temperature
3 °C
Number of pumps
Materials
Gasket material
EPDM 
Shaft
Stainless steel 
Pump housing
Ductile cast iron 
Pipework material
Steel 
Dimension, weight
Width
2678 mm
Net weight, approx.
1645 kg
Length
1582 mm
Gross weight, approx.
1675 kg
Height with packaging
2575 mm
Height
2445 mm
Length with packaging
1782 mm
Width with packaging
2878 mm
Installation dimensions
Pipe connection on the suction side
DN 125 
Pipe connection on the discharge side
DN 150 
Packaging
Packaging type
Special pallet 
Packaging property
Sales packaging 
Pieces per pallet
Number per layer
Артикул Название Цена
4241569 SiFire-EN-65/250-248-37D 25432810
4241601 SiFire-EN-100/315-318-197D 59789980
4241580 SiFire-EN-80/200-224-47,7D 27039720
4241614 SiFire-EN-32/250-246-17,7DJ 21005980
4241591 SiFire-EN-100/200-212-47,7D 28066890
4241570 SiFire-EN-65/250-258-47,7D 26152435
4241604 SiFire-EN-125/250-266-197D 52504345
4241581 SiFire-EN-80/200-228-47,7D 27129610
4241592 SiFire-EN-100/200-222-66D 29260710
4241571 SiFire-EN-65/250-264-47,7D 26213540
4241605 SiFire-EN-125/250-274-197D 52686145
4241582 SiFire-EN-80/250-235-66D 29108200
4241593 SiFire-EN-100/200-228-66D 29488970
4241572 SiFire-EN-65/315-295-66D 34980845
4241606 SiFire-EN-32/200-154-4,2DJ 17049305
4241583 SiFire-EN-80/250-243-66D 32481600
4241594 SiFire-EN-100/250-255-100D 34945495
4241573 SiFire-EN-65/315-305-100D 40096495
4241607 SiFire-EN-32/200-172-6,8DJ 17219995
4241584 SiFire-EN-80/250-254-100D 34078410
4241563 SiFire-EN-65/200-185-17,7D 21014565
4241595 SiFire-EN-100/250-260-100D 35467160
4241574 SiFire-EN-65/315-316-100D 39733400
4241608 SiFire-EN-32/200-182-6,8DJ 17289180
4241585 SiFire-EN-80/250-270-100D 34241020